PEERLESS OVENS: HOME OF THE "MAXIMIZER"

C131P Setup & Calibration

A qualified service technician must perform the following in this order:


  1. MANIFOLD Operating Gas Pressure must be checked:
    NAT GAS – it should be 4” of water column, as measured using a monometer
    LP GAS – it should be 10” of water column, as measured using a monometer

  2. BYPASS must be set – this ensures the low flame setting on the burners is correct (see attached instructions)

  3. THERMOSTAT must be calibrated (see attached instructions)

NOTE: The top deck is the primary deck and should always be used first when cooking


STARTUP CHECKLIST BJWA THERMOSTAT CALIBRATION FDTO THERMOSTAT CALIBRATION